| | Continuity | | |
| | |
| | |
| | | | | | |
| | | | Range | | | | |20/200/2000Ω (Auto-ranging) | | |
| | | | | | |
| | |
| | | | | | |
| | | | Open circuit voltage (DC) | | | | |5V±20% (*1) | | |
| | | | | | |
| | |
| | | | | | |
| | | | Short circuit current | | | | |Greater than 200mA | | |
| | | | | | |
| | |
| | | | | | |
| | | | Accuracy | | | | |±0.1Ω (0~0.19Ω) |±2%rdg+8dgt (0.2~2000Ω) | | |
| | | | | | |
|
| | |
| | Insulation Resistance | | |
| | |
| | |
| | | | | | | | |
| | | | Range | | | | |20/200MΩ |(Auto-ranging) | | | | |20/200/2000MΩ (Auto-ranging) | | |
| | | | | | | | |
| | |
| | | | | | | | | | |
| | | | Open circuit voltage (DC) | | | | |250V+25% -0% | | | | |500V+25% -0% | | | | |1000V+20% -0% | | |
| | | | | | | | | | |
| | |
| | | | | | | | | | |
| | | | Rated current | | | | |1mA or greater |@ 250kΩ | | | | |1mA or greater |@ 500kΩ | | | | |1mA or greater |@ 1MΩ | | |
| | | | | | | | | | |
| | |
| | | | | | | | |
| | | | Accuracy | | | | |±2%rdg+6dgt (0~19.99MΩ) |±5%rdg+6dgt (20~200MΩ) | | | | |±2%rdg+6dgt (0~199.9MΩ) |±5%rdg+6dgt (200~2000MΩ) | | |
| | | | | | | | |
|
| | |
| | Loop Impedance | | |
| | |
| | |
| | | | | | | | | | |
| | | | Function | | | | |L-PE | | | | |L-PE (ATT) | | | | |L-N / L-L | | |
| | | | | | | | | | |
| | |
| | | | | | | | |
| | | | Rated Voltage | | | | |100~260V 50/60Hz | | | | |L-N: 100~300V |L-L: 300~500V 50/60Hz | | |
| | | | | | | | |
| | |
| | | | | | | | | | |
| | | | Nominal Test Current at 0Ω External Loop: Magnitude / Duration (*2) | | | | |20Ω: 6A/20ms |200Ω: 2A/20ms |2000Ω: 15mA/500ms | | | | |L-N: 6A/60ms |N-PE: 10mA/approx. 5s | | | | |20Ω: 6A/20ms | | |
| | | | | | | | | | |
| | |
| | | | | | | | | | |
| | | | Range | | | | |20/200/2000Ω |(Auto-ranging) | | | | |20/200/2000Ω |(Auto-ranging) |(L-N < 20Ω) | | | | |20Ω | | |
| | | | | | | | | | |
| | |
| | | | | | | | | | |
| | | | Accuracy | | | | |±3%rdg+4dgt (*3) |±3%rdg+8dgt (*4) | | | | |±3%rdg+6dgt (*3) |±3%rdg+8dgt (*4) | | | | |±3%rdg+4dgt (*3) |±3%rdg+8dgt (*4) | | |
| | | | | | | | | | |
|
| | |
| | PSC (L-N / L-L) / PFC (L-PE) | | |
| | |
| | |
| | | | | | | | | | |
| | | | Function | | | | |PSC | | | | |PFC | | | | |PFC (ATT) | | |
| | | | | | | | | | |
| | |
| | | | | | | | | | |
| | | | Rated Voltage | | | | |100~500V 50/60Hz | | | | |100~260V 50/60Hz | | | | | | | |
| | | | | | | | | | |
| | |
| | | | | | | | | | |
| | | | Nominal Test Current at 0Ω External Loop: Magnitude / Duration (*5) | | | | |6A/20ms | | | | |6A/20ms |2A/20ms |15mA/500ms | | | | |L-N: 6A/60ms |N-PE: 10mA/approx. 5s | | |
| | | | | | | | | | |
| | |
| | | | | | |
| | | | Range | | | | |2000A/20kA Auto-Ranging | | |
| | | | | | |
| | |
| | | | | | |
| | | | Accuracy | | | | |PSC / PFC accuracy is derived from measured loop impedance |specification and measured voltage specification | | |
| | | | | | |
|
| | |
| | RCD | | |
| | |
| | |
| | | | | | | | | | | | | | |
| | | | Function | | | | |X1/2 | | | | |X1 | | | | |X5 | | | | |Ramp | | | | |Auto | | |
| | | | | | | | | | | | | | |
| | |
| | | | | | | | | | | | |
| | | | Trip current setting | | | | |10/30/100/300/ |500/1000mA | | | | |10/30/ |100mA | | | | |10/30/ |100/300/ |500mA | | | | |Depending on the |accuracy at each |function. |Measurement sequence: |X1/2 0°→X1/2 180° |→X1 0°→X1 180° |→X5 0°→X5 180° |Measurements with |x5 are not carried out |for RCDs with |nominal current of |100mA or more. | | |
| | | | | | | | | | | |
| | | |
| | | | | | | | | | | | | |
| | | | Trip current Duration | | | | |2000ms | | | | |G: 550ms |S: 1000ms | | | | |410ms | | | | |Goes up by |10% from 20% to |110% |G:300ms/ |S:500ms |X10 times | | | |
| | | | | | | | | | | | | |
| | | |
| | | | | | | |
| | | | Rated Voltage | | | | |230V+10%-15% 50/60Hz | | | |
| | | | | | | |
| | | |
| | | | | | | | | | | |
| | | | Accuracy | | | | |AC Type: |-8%~-2% |A Type: |-10%~0% | | | | |AC Type: +2%~+8% |A Type: 0%~+10% | | | | |AC Type: ±4% |A Type: ±10% | | | |
| | | | | | | | | | |
| | | | |
| | | | | | |
| | | | | |Trip time: ±1%rdg+3dgt | | | |
| | | | | | | | |
|
| | |
| | RCD (Uc) | | |
| | |
| | |
| | | | | | |
| | | | Function | | | | |UC | | |
| | | | | | |
| | |
| | | | | | |
| | | | Rated Voltage | | | | |230V+10%~15% 50/60Hz | | |
| | | | | | |
| | |
| | | | | | |
| | | | Range | | | | |100.0V | | |
| | | | | | |
| | |
| | | | | | |
| | | | Test current | | | | |≤ 1/2IΔn (max150mA) | | |
| | | | | | |
| | |
| | | | | | |
| | | | Accuracy | | | | |+5%~+15%rdg, ±8dgt | | |
| | | | | | |
|
| | |
| | Earth | | |
| | |
| | |
| | | | | | |
| | | | Range | | | | |20/200/2000Ω Auto-Ranging | | |
| | | | | | |
| | |
| | | | | | |
| | | | Accuracy | | | | |20Ω: ±3%rdg+0.1Ω |200/2000Ω: ±3%rdg+3dgt (Auxiliary earth resistance 100±5%) | | |
| | | | | | |
|
| | |
| | Phase Rotation | | |
| | |
| | |
| | | | | | |
| | | | Rated voltage | | | | |50-500V 50/60Hz | | |
| | | | | | |
| | |
| | | | | | |
| | | | Remarks | | | | |Correct phase sequence: are displayed "1.2.3" and mark |Reversed phase sequence: are displayed "3.2.1" and mark | | |
| | | | | | |
|
| | |
| | Volts | | |
| | |
| | |
| | | | | | | | |
| | | | Function | | | | |Volts | | | | |Frequency | | |
| | | | | | | | |
| | |
| | | | | | |
| | | | Rated voltage | | | | |25~500V, 45~65Hz | | |
| | | | | | |
| | |
| | | | | | | | |
| | | | Measuring range | | | | |25~500V | | | | |45~65Hz | | |
| | | | | | | | |
| | |
| | | | | | | | |
| | | | Accuracy | | | | |±2%rdg+4dgt | | | | |±0.5%rdg+2dgt | | |
| | | | | | | | |
|
| | |
| | General | | |
| | |
| | |
| | | | | | |
| | | | Applicable standards | | | | |IEC 61010-1 CAT.III 300V (500V L to L) Pollution degree 2, IEC 61010-031, |IEC 61557-1, 2, 3, 4, 5, 6, 7, 10, IEC 60529 (IP40), IEC 61326 (EMC) | | |
| | | | | | |
| | |
| | | | | | |
| | | | Power source | | | | |LR6 X 8 | | |
| | | | | | |
| | |
| | | | | | |
| | | | Dimensions | | | | |136(L) X 235(W) X 114(D)mm | | |
| | | | | | |
| | |
| | | | | | |
| | | | Weight | | | | |1350g (including batteries.) | | |
| | | | | | |
| | |
| | | | | | |
| | | | Accessories | | | | |7188A (Distribution board fuse test lead set) |7196A (Test leads with remote control switch) |7218A (Power cord [EU]) (*6) |7228A (Earth resistance test leads) |8032 (Auxiliary earth spikes) |8212-USB (USB adaptor with KEW Report (Software)) |9142 (Carrying case) |9121 (Shoulder strap) |Cord case, Buckle, Battery, Instruction manual | | |
| | | | | | |
| | |
| | | | | | |
| | | | Optional | | | | |8212-RS232C (RS232C adaptor with KEW Report (Software)) | | |
| | | | | | |
|